2. ELECTRICAL ENGINEERING SCORE: 6.0/10 Strengths: - Uses the correct 3-phase voltage-drop equation with R·cosφ + X·sinφ. - Correctly calculates 252 A starting current and handles the 0.30 starting PF. - Numerical cable-drop calculations are internally consistent with the stated R/X assumptions. - Correctly separates ampacity from voltage-drop performance. Major errors: - Direct contradiction: first says X·sinφ is "dominant," then correctly calculates it as only ~17% of cable impedance drop. - Treats 5% as a NEMA MG 1 starting-voltage-drop limit; that is not a general motor-start acceptance criterion. - Actual starting terminal sag cannot be assessed from cable impedance alone; transformer/source impedance is essential. - NEC motor conductor sizing is not simply 42 A < 65 A. Motor conductor rules generally involve 125% of applicable motor FLC plus installation/termination/derating requirements. - Assumes THHN/THWN-2 and a 75°C ampacity column despite those conditions not being given. - The assumed 0.10 mΩ/m reactance is plausible only as an estimate and materially affects the starting result. Verdict: Good engineering mathematics, but insufficient code discipline and an overconfident final "pass." The defensible conclusion is that 6 AWG appears plausible for cable voltage drop under stated assumptions, while total starting-voltage performance and NEC compliance remain unproven.